HeatCore C1

Low System Pressure Warning

Symptoms

Likely Causes

Step-by-step Fix

  1. Locate the filling loop. This is a braided flexible hose located beneath the boiler. It connects the mains cold water supply to the central heating circuit. You will see two small valves — one at each end of the hose.
  2. Open the first filling valve. Turn it a quarter turn so that the handle aligns with the pipe. You will not hear anything yet.
  3. Slowly open the second filling valve. Turn it gradually. You will hear water flowing into the system. Open it slowly — fast filling can introduce air pockets.
  4. Watch the pressure gauge. The needle will begin to rise. Fill the system until the gauge reads between 1.0 and 1.5 bar (the green zone).
  5. Close the second valve first, then close the first valve. Both handles should be perpendicular to the pipe when fully closed.
  6. Check the pressure holds. Turn the heating on and run it for 30 minutes, then check the pressure again. A slight rise during heating (up to 2.0 bar) is normal. When the system cools, it should settle back to 1.0–1.5 bar.

Pressure keeps dropping?

If you need to repressurise the system more than once every few months, there is likely a leak somewhere in the heating circuit. Check visible pipework and radiator valves for signs of damp or dripping. A leak may also be hidden under flooring or behind walls. Contact a heating engineer to carry out a pressure test and locate the source. Do not keep topping up the system indefinitely — frequent filling introduces fresh oxygenated water, which accelerates internal corrosion.